Thermal Magnetic Residual MCCB TDK1L

TDK1L series molded case circuit breaker is used for AC 50/60Hz, rated working voltage of 400V,  rated insulation voltage of 800V, rated working current up to 630A. Used for frequent conversion in circuit and infrequent starting of motor. The rated residual operating current and the maximum breaking time can be adjusted according to the actual situation. Be able to protect lines and power supply equipment from damage, and can also provide protection against long-term grounding faults that cannot be detected by overcurrent protection, which may cause fire hazards. The conventional leakage protection module with residual current protection circuit breaker is sampled as two phases, and this series of circuit breakers is three phases. If any phase is lost, the leakage protection module of circuit breaker can still work normally.

    Scope of Application

    TDK1L series molded case circuit breaker is used for AC 50/60Hz, rated working voltage of 400V,rated insulation voltage of 800V, rated working current up to 630A.

    Used for frequent conversion in circuit and infrequent starting of motor.The rated residual operating current and the maximum breaking time can be adjusted accordingto the actual situation.

    Be able to protect lines and power supply equipment from damage, and can also provide protectionagainst long-term grounding faults that cannot be detected by overcurrent protection, which maycause fire hazards.

    The conventional leakage protection module with residual current protection circuit breakeris sampled as two phases, and this series of circuit breakers is three phases. If any phase is lost, theleakage protection module of circuit breaker can still work normally.

    Comply with IEC60947-2 standard.With the functions of overload, short circuit, leakage and undervoltage protection.With leakage alarm output function.Comply the electromagnetic compatibility requirements of Appendix B in IEC60947The full series of circuit breakers has isolation function, and its symbol is_

    Model and Meaning

    未标题-2.jpg

    Serial No. Item meaning
    Enterprise code:TALEMOD
    MCCB(Molded Case Circuit Breaker)
    Design No.
    Power leakage
    Frame grade current(A)optional code:Inm=125,Inm=250,Inm=400,Inm=630,Inm=800
    Ultimate short circuit breaking capacity:L:Standard(25,35,50kA);M:Middle breaking (50,65kA);H:High breaking(50,80kA)
    Operation mode:P:Electric operation;Z:Operate by rotating handle
    No.of poles:3:three-pole,4:four-pole
    Release mode and optional codes for internal accessories
    Optional codes for different purposes:No code:For power distribution, 2:For motor protection,Th:For "three-prevention"occasions
    4-pole product code
    Types of residual current protection Optional:
    Non-delay -type I;Delay-type I(the parameters are not adjustable)
    Non-delay -typeII;Delay -type Ⅱ(the parameters are adjustable) Alarm type (adjustable parameters)
    Rated curent
    Installation modes are optional:
    Front wiring of board;Rear wiring of board;Plug-in wiring; Special mode(negotiated by user and factory)

    Main Technical Parameters

    Technical performance indicators

    Model TDK1L-125 TDK1L-250 TDK1L-400 TDK1L-630 TDK1L-800
    Frame grade current Inm(A) 125 250 400 630
    Rated curent In(A) (10),16,20,25,32,40, 50,63,80,100,125 100,125,140,160,
    180,200,225,250
    225,250,315,
    350,400
    400,500,
    630,700,800
    No.of poles 3 4 3 4 3 4 3 4
    Rated insulation voltage Ui(V) 800
    Rated operating voltage Ue(V) AC400
    Rated impulse withstand voltage Uimp(kV) 8
    Flashover distance (mm) 50 100
    Breaking capacity level L M L M H L M L M H L M H L M H
    Ultimate short-circuit breaking capacity Icu(kA) AC400V 50 85 25 35 50 50 85 25 50 85 50 65 100 50 65 100
    Operating short-circuit AC400V 35 50 18 22 35 35 50 18 35 50 35 42 65 35 42 65
    breaking capacity Ics(kA)
    Rated residual short circuit on (off)capacity I△m(kA) 1/4lcu
    Rated residual operating current I△n(mA) Non-delay type 30/100/500/ 30/100/500/ 100/300/500 300/500/1000
    100/300/500 100/300/500
    Delay time 100/300/500 100/300/500 100/300/500 300/500/1000
    Rated residual non-operating curent I△no(mA) 1/2I△n 1/2I△n 1/2I△n 1/2I△n
    Operational performance (times) Powered 1500 1000 1000 1000
    Not powered 8500 7000 4000 4000
    Total 10000 8000 5000 5000
    Residual current protection operation time I△n 2I△n 5I△n 10I△n
    Maximum breaking time (s) Non-delay type 0.3 0.15 0.04 0.04
    Delay time 0.4/1 0.4/1 0.4/1 0.4/1

    Note: The maximum breaking time of delay type can be customized according to requirements of customers.