Leave Your Message

Thermal Magnetic MCCB TDK5

TDK5 series molded case circuit breaker with rated insulation voltage of 1000V is suitable for infrequent switching and infrequent starting of motor in circuits with frequency of AC 50Hz, rated working voltage of 415V and rated working current of 800AThe circuit breaker has the functions of overload, short circuit and undervoltage protection, which can protect the circuit and power supply equipment from damage.

    Scope of Application

    TDK5  series  molded  case  circuit  breaker(hereinafter  referred  to  as  circuit  breake)with  rated  insulation  voltage  of  1000V  is  suitable  for  infrequent  switching  and  infrequent  starting  of  motor in circuits with frequency of AC 50Hz,rated workng voltage of 415V and rated working current of 800A. The  circuit  breaker  has  the  functions  of  overload,short  circuit  and  undervoltage  protection,which can  protect  the  circuit  and  power  supply  equipment  from  damage.

    Circuit  breaker  can  be  installed  vertically  (i.e.vertically)or  horizontally  (i.e.transversely).

    Circuit  breaker  has  isolation  function,and  their  corresponding  symbols  are:   .

    Circuit  breaker  products  shall  comply  with  the  following  standards:

    IEC60947-1  General

    IEC60947-2  Low Voltage  Circuit  Breaker

    IEC60947-4-1  Electromechanical  Contactors  and  Motor  Starters

    IEC60947-5-1  Electromechanical  Control  Circuit  Electrical  Appliance

    Model and Meaning

    未标题-1.jpg

    Serial No. Item meaning
    Enterprise code:TALEMOD
    MCCB(Molded Case Circuit Breaker)
    Design No.
    Frame grade current(A):Inm=63,Inm=100,Inm=125i,Inm=125,Inm=160,Inm=250, Inm=400,Inm=630i,Inm=800
    i:Capacity expanion current;Conventional no code
    Breaking capacity:C:Low breaking;S:Ordinary breaking;L:Middle breaking;M:High breaking
    Surface cover type:S:Single-cap;Double-cap no code
    Operating mode:Manual direct operation:no code;Z:Operate by rotating handle; P:Electric operation
    No.of poles:3:three-pole;4:four-pole
    Release mode and accessory code
    4-pole product code;3-pole product no code

    Note: 4-pole product code
    Type A: Overcurrent tripping element is not installed at N pole, and N pole is always ON andnot combined with other three poles.
    Type B: Overcurrent tripping element is not installed at N pole, and N pole is combined with otherthree poles (N pole is combined first and then separated).

    Main Technical Parameters

    Model TDK5-63
    TDK5-100
    TDK5-125i
    TDK5-125
    TDK5-160
    TDK5-250 TDK5-400 TDK5-630i TDK5-800
    Frame grade curent Inm(A) 63,100,125i 125,160 250 400,630i 800
    Rated current In(A) 10,16,20,25,
    32,40,50,63,
    80,100,125
    16,20,25,32,
    40,50,63,80,
    100,125,
    140,160
    100,125,140,
    160,180,200,
    225,250
    225,250,315,
    350,400,500,
    630
    630,700,
    800
    No.of poles 3 4 3 4 3 4 3 4 3 4
    Rated insulation voltage Ui(V) 800 1000
    Rated operating voltage Ue(V) AC400,AC415
    Rated impulse withstand voltage Uimp(kV) 8 12
    Flashover distance(mm) 50 100
    Breaking capacity level C S L M C S L M C S L M C S L M C S L M
    Ultimate short-circuit breaking capacity Icu(kA) 15 25 35 50 25 35 36 50 25 35 36 50 42 50 50 70 42 50 50 70
    Operating short-circuit breaking capacity Ics(kA) 10 18 21 30 15 7.5 25 36 15 18 25 36 25 25 50 70 25 36 50 70
    Operational performance (times) Powered 1500 1500 1000 1000 500
    Not powered 8500 8500 7000 4000 2500
    Total 10000 10000 8000 5000 3000

    Protection Characteristics

    Power distribution

    Rated current (A) Thermal release (ambient temperature+40℃) Operating current of electromagnetic release(A)
    1.05In (cold)non-operating time (h) 1.3In(hot)operating time(h)
    16≤In≤63 Non-operating within 1 hour ≤1 10A-40A:400A±20% 50A-800A:10In±20%
    63<In≤800 Non-operating within 2 hours ≤2

    For protecting motors

    Rated current (A) Thermal release (ambient temperature+40℃) Operating
    current of
    electromagnetic release(A)
    1.0In  (cold) non-operating
    time(h)
    1.2In(hot)
    operating time(h)
    1.5In(hot)
    operating time(h)
    7.2In(cold)
    operating
    time(h)
    Trippinglevel 10A-40A:  400A±20% 50A-800A: 12In±20%
    10≤In≤25 Non-operating within 2 hours ≤2 ≤2min 0.5s<Tp≤5s 5
    25<In≤250 ≤4min 4s<Tp≤10s 10
    250<In≤800 ≤8min 6s<Tp≤20s 20

    Classification of Circuit Breakers 

    Classified according to the number of poles: 3-pole and 4-pole;
    Classified according to the application: For power distribution and motor protection;
    Classiied according to the operation modes, Operated by handle, electric operation (denoted by p), operated by rotating handle idenoted