Thermal Magnetic MCCB TDK2
Model and Meaning

| Serial No. | Item meaning |
| ① | Enterprise code:TALEMOD |
| ② | MCCB(Molded Case Circuit Breaker) |
| ③ | Design No. |
| ④ | Frame grade current(A)optional code:Inm=63,Inm=125,Inm=250,Inm=400,Inm=630,Inm=800 |
| ⑤ | UItimate short circuit breaking capacity:L:Standard (25,35,50kA);M:High breaking(50,65kA) |
| ⑥ | Operation mode: Manual direct operation: no code; Z: Operate by rotating handle;P: Electric operation |
| ⑦ | No.of poles:,3:three-pole,4:four-pole |
| ⑧ | Release mode and accessory code |
| ⑨ | Code:For distribution: no code; 2: For motor protection |
| ⑩ | Rated current(See Technical Parameters in Table) |
| ⑪ | 4-pole product code; 3-pole product no code |
| ⑫ | Installation modes are optional:Front wiring of board;Rear wiring of board;Plug-in wiring Special mode(negotiated by user and factory) |
| ⑬ | Other accessories are optional:Mechanical interlocking between two circuit breakers |
Note: 4-pole product code
Type A: Overcurrent tripping element is not installed at N pole, and N pole is always ON and notcombined with other three poles.
Type B: Overcurrent tripping element is not installed at N pole, and N pole is combined with otherthree poles (N pole is combined first and then separated).
Type C: Overcurrent tripping element is installed at N pole, and N pole is combined with other threepoles (N pole is combined first and then separated).
Type D: Overcurrent tripping element is installed at N pole, and N pole is always ON and not combinedwith other three poles.
Main Technical Parameters
| Model | TDK2-63 | TDK2-125 | TDK2-250 | TDK2-400 | TDK2-630 | TDK2-800 | |||||||||
| Frame grade current Inm(A) | 63 | 125 | 250 | 400 | 630 | 800 | |||||||||
| Rated current In(A) | 10,16,20,25, 32,40,50,63 |
16,20,25,32, 40,50,63,80, 100,125 |
100,125,140, 160,180,200, 225,250 |
225,250,315, 350,400 |
400,500, 630 |
630,700, 800 |
|||||||||
| No.of poles | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | |||
| Rated insulation voltage Ui(V) | 800 | 1000 | |||||||||||||
| Rated operating voltage Ue(V) | AC400 | AC400,AC690 | |||||||||||||
| Rated impulse withstand voltage Uimp(kV) | 8 | 12 | |||||||||||||
| Flashover distance(mm) | 50 | 100 | |||||||||||||
| Breaking capacity level | L | M | H | L | M | H | M | H | M | H | M | H | |||
| Ultimate short-circuit breaking capacity Icu(kA) |
AC690V | ||||||||||||||
| AC400V | 25 | 50 | 70 | 100 | 50 | 70 | 100 | 70 | 100 | 70 | 100 | 75 | 100 | ||
| Operating short-circuit breaking capacity Ics(kA) |
AC690V | ||||||||||||||
| AC400V | 18 | 35 | 50 | 70 | 35 | 50 | 70 | 70 | 75 | 70 | 75 | 75 | 75 | ||
| Operational performance (times) | Powered | 1500 | 1500 | 1000 | 1000 | 1000 | 500 | ||||||||
| Not powered | 8500 | 8500 | 7000 | 4000 | 4000 | 2500 | |||||||||
| Total | 10000 | 10000 | 8000 | 5000 | 5000 | 3000 | |||||||||
Scope of Application
TDK2 series molded case circuit breaker (hereinafter referred to as circuit breaker) with ratedinsulation voltage of 1000V is suitable for infrequent switching and
infrequent starting of motor incircuits with frequency of 50Hz AC, rated working voltage of 690V and below, and rated workingcurrent of 800A(TDK2-800 without
protection motor).
The circuit breaker has the functions of overloadshort circuit and undervoltage protection, which can protect the circuit and power supply equipmentfrom damage.
Three adjustable delay functions are added to the product, which are 0.8xIn, 0.9xIn,1.0xIn respectively.
Circuit breaker can be installed vertically (i.e. vertically) or horizontally (i.e. transversely).Circuit breaker has isolation function, and its corresponding symbol is:
Circuit breaker products comply with the following standards:
IEC60947-1 General
IEC60947-2 Low Voltage Circuit Breaker
IEC60947-4-1 Electromechanical Contactors and Motor Starters
IEC60947-5-1 Electromechanical Control Circuit Electrical Appliance
Protection Characteristics
For power distribution
| Rated current (A) | Thermal release (ambient temperature+40℃) | Operating current of electromagnetic release(A) | |
| 1.05In(cold)non-operating time (h) | 1.3In(hot)operating time(h) | ||
| 10≤In≤63 | Non-operating within 1 hour | ≤1 | 10In±20% |
| 63<In≤100 | Non-operating within 2 hours | ≤2 | |
| 100<In≤800 | Non-operating within 2 hours | ≤2 | 5In±20%,10In±20% |
For protecting motors
| Circuit breaker model | Thermal release (ambient temperature+40℃) | Operating current of electromagnetic release(A) | ||||
| 1.0In (cold) non-operating time(h) |
1.2In(hot) operating time(h) |
1.5In(hot) operating time(h) |
7.2In(cold) operating time(h) |
Tripping level | ||
| TDK2-63L,M,H | Non-operating within 2 hours | ≤2 | ≤2min | 0.5s<Tp≤5s | 5 | 12In±20% |
| TDK2-125L,M,H | ≤4min | 4s<Tp≤10s | 10 | |||
| TDK2-250L,M,H TDK2-400M,H TDK2-630M,H TDK2-800M,H |
≤8min | 6s<Tp≤20s | 20 | |||
Note: The operating current value of 10 ~ 25A electromagnetic trip of TDK2-63 L, M is 300A±20%