Thermal Magnetic MCCB TDK1

TDK1 series molded case circuit breaker is used for AC 50/60Hz, rated working voltage of 400V,rated insulation voltage of 800V for type 63 and 1000V for type 125-800, rated working current up to800A. Used for frequent conversion in circuit and infrequent starting of motor. With overload, short circuit and undervoltage protection functions. With the features of compact structure, small volume, high breaking capacity and zero flashover. Reasonable design, safe and reliable, beautiful appearance,All accessories are available, easy to install, convenient to use, and highly adaptable.

    Scope of Application

    TDK1 series molded case circuit breaker is used for AC 50/60Hz, rated working voltage of 400V,rated insulation voltage of 800V for type 63 and 1000V for type 125-800, rated working current up to800A.

    Used for frequent conversion in circuit and infrequent starting of motor.

    Comply with IEC60947-2 standard.

    With overload, short circuit and undervoltage protection functionsWith the features of compact structure, small volume, high breaking capacity and zero flashover.High breaking capacity: up to 65kA.

    Reasonable design, safe and reliable, beautiful appearance.All accessories are available, easy to install, convenient to use, and highly adaptable.The whole series of circuit breakers has isolation function, and its symbol is:

    Model and Meaning

    未标题-4.jpg

    Serial No.     Item meaning
    Enterprise code:TALEMOD
    MCCB(Molded Case Circuit Breaker)
    Design No.
    Frame grade current(A)optional code:Inm=63,Inm=125,Inm=250,Inm=400,Inm=630,Inm=800
    UItimate short circuit breaking capacity:L:Standard (25,35,50kA);M:High breaking(50,65kA)
    Operation mode: P:Electric operation;Z:Operate by rotating handle
    No.of poles:2:two-pole,3:three-pole,4:four-pole
    Release mode and optional codes for internal accessories
    Optional codes for different purposes:No code:For power distribution,2:For motor protection,Th:For "three-prevention"occasions
    4-pole product code
    Rated current
    Installation modes are optional:Front wiring of board;Rear wiring of board;Plug-in wiring Special mode(negotiated by user and factory)
    Other accessories are optional:Mechanical interlocking between two circuit breakers

    Note: 4-pole product code

    Type A: Overcurrent tripping element is not installed at N pole, and N pole is always ON and notcombined with other three poles
    Type B: Overcurrent tripping element is not installed at N pole, and N pole is combined with otherthree poles.
    Type C: Overcurrent tripping element is not installed at N pole, and N pole is combined with otherthree poles.
    Type D: Overcurrent tripping element is not installed at N pole, and N pole is always ON and notcombined with other three poles

    Main Technical Parameters

    Model TDK1-63 TDK1-125 TDK1-250 TDK1-400 TDK1-630 TDK1-800
    Frame grade current Inm(A) 63 125 250 400 630 800
    Rated current In(A) 10,16,20,25,
    32,40,50,63
    16,20,25,32,
    40,50,63,80,
    100,125
    100.125.140,160,180,200,225,250 225,250,315,
    350,400
    400,500,
    630
    630,700,
    800
    No.of poles 3 4 3 4 3 4 3 4 3 4 3 4
    Rated insulation voltage Ui(V) 800 1000
    Rated operating voltage Ue(V) AC400 AC400,AC690
    Rated impulse withstand voltage Uimp(kV) 8 12
    Flashover distance(mm) 50 100
    Breaking capacity level L M L M L M L M H L M L M
    Ultimate short-circuitbreaking capacityIcu(kA) AC690V 20 20 20 20 30
    AC400V 25 50 35 50 35 50 50 65 100 50 65 50 75
    Operating short-circuit breaking capacity
    Ics(kA)
    AC690V 15 15 15 15 20
    AC400V 18 35 22 35 22 35 35 42 65 35 42 35 50
    Operational performance (times) Powered 1500 1500 1000 1000 1000 500
    Not powered 8500 8500 7000 4000 4000 2500
    Total 10000 10000 8000 5000 5000 3000

    Protection Features

    The thermal release of circuit breaker has inverse time limit feature; The electromagnetic release is instantaneous operating, and the featuresare shown in Table 3 (for power distribution) and Table 4 (for motor protection).

    Rated current of release (A) Thermal elease(ambient temperature  For land +40°C/For ship +45°℃) Operating current of electromagnetic release(A)
    1.05 In(cold)non-operating time (h) 1.30In(hot)operating time (h)
    110≤In≤63 ≥1 <1 10In±20%
    63<In≤100 ≥2 <2
    100<In≤800 ≥2 <2 51n±20%,10In±20%
    Rated current (A) Thermal elease(ambient temperature  For land +40°C/For ship +45°℃) Operating current of
    electromagnetic
    release (A)
    1.0In(cold).
    non-operating time
    1.2In  (hot)
    operating time (h)
    1.5In(hot)
    operating time (h)
    7.2In(cold)
    operating time (h)
    10≤In≤225 ≥2 <2 <4min 4s<Tp≤10s 12In±20%
    225<In≤630 <8min 6s<Tp≤20s