Leave Your Message

Smart Residual MCCB(Reclosing Type)TDK5EL

The rated insulation voltage of smart residual molded case circuit breaker (smart reclosing type) is 1000V, which is suitable for three-phase four-wire neutral point direct grounding (TT) distribution networks with AC 50Hz, 400V rated voltage and 630A rated current. It is used to provide indirect contact protection. Prevent fire danger caused by grounding fault current due to equipment insulation damage. And it can be used to distribute electric energy and it can also be used to distribute electric energy and protect lines and power supply equipment from overload, undervoltage, short circuit, single-phase grounding and other faults.

The products conform to IEC60947-2 standard.

    Model and Meaning

    未标题-3.jpg

    Serial No. Item meaning
    Enterprise code:TALEMOD
    MCCB(Molded Case Circuit Breaker)
    Design No.
    Electronic &adjustable
    With residual current protection
    Frame grade current (A)Inm=125,Inm=250,Inm=400,Inm=630
    Automatic reclosing of leakage trip
    Y:LCD;S:Digital

    Main Technical Parameters

    Model TDK5EL-125CY
    TDK5EL-125CS
    TDK5EL-250CY
    TDK5EL-250CS
    TDK5EL-400CY
    TDK5EL-400CS
    TDK5EL-630CY
    TDK5EL-630CS
    Frame grade curent Inm(A) 125 250 400 630
    No.of poles 3P+N 3P+N 3P+N 3P+N
    Rated operating voltage Ue(V) AC400/50Hz
    Rated insulation voltage Ui(V) 800 1000
    Rated impulse withstand voltage Uimp(kV) 8
    Flashover distance(mm) ≯50 ≯100
    Ultimate short-circuit breaking capacity Icu(kA) 50 65 85
    Operating short-circuit breaking capacity Ics(kA) 35 42 65
    Rated residual short-circuit making (breaking) capacity I△m(kA) 12.5 16.25 21.25
    Rated short-time withstand current Icw(kA)/s 1.5 3 5 8
    Residual current operating characteristics AC type
    Rated residual operating curent I△n(mA) 50/100/200/300/400/500/600/800
    MCU automatic tracking or manual setting
    100/200/300/400/500/600/800/
    1000 MCU automatic tracking or manual setting
    Residual operating time characteristics Delayed/non-delayed type
    Limit non-drive time of delayed type(s) 0.06:2I△n
    Breaking time (s) I△n≤0.5;2I△n≤0.2;5I△n≤0.15
    Auto reclosing time (s) 20~60
    Operational performance (times) Powered 1500 1000 1000
    Not powered 8500 7000 4000
    Total 10000 8000 5000
    Overload and short circuit characteristics Three-stage protection,electronically adjustable,see "Description of Protection Characteristics"for details
    Overvoltage protection value (V) Set value (250~300)±5%
    Undervoltage protection value (V) Set value(145~200)±5%
    Link control delay time(ms) ≤40ms
    Communication delay time(ms) ≤200ms

    Main Functions and Featuresr

    High-performance 32-bit ARM microprocessor is used to carry out signal processing and intelligent control in real time;

    LCD Chinese/English display provides friendly HMI and simple operation;

    For residual current (leakage)protection,the residual current gear can be set online,with reclosing function;

    Monitor and track the residual current of the line in real time,and automatically adjust the gear to ensure the operation rate and reliability of the product;

    Long delay,short delay and instantaneous three-stage protection,electronic tripping mode is applied, which is independent of supply voltage;

    High breaking capacity could ensure the reliability of short circuit protection for the line;

    Overvoltage  protection,undervoltage  protection,phase  loss  protection;

    Real-time display of residual current,three-phase supply voltage and load current of the line;

    Protection functions and parameters can be set and modified online;

    Trip types(residual current,locking,overload,undervoltageovervoltage,phase loss)can be identified &displayed,and  can  be  stored,inquired  &deleted;

    Network type has communication function,which can realize remote communication,telemetry,remote control and remote adjustment;

    Pluggable  lightning  protection  module(optional);

    Infrared communication function (optional).