MCB Accessories for TDM5 (AL5, AU5, SH5, UV5)

AL(Alarm Contact), AU(Auxiliary Contact), SH(Shunt Release), UV(Under-Voltage Release) 

    Product Introduction

    1. AL - Alarm Contact
    Function: A mechanical, non-powered signal contact. It changes state only when the breaker trips automatically due to overload or short circuit.
    Purpose: Provides a remote signal for fault tripping, used for alarms and fault identification. It does not operate during manual switching.
    Key Feature: Requires no external power supply; it outputs a signal through the mechanical movement of the microswitch.

    2. AU - Auxiliary Contact
    Function: A mechanical, non-powered signal contact. It real-time reflects the mechanical position (ON or OFF) of the breaker's main contacts.
    Purpose: Used for remote status monitoring. Its state changes whenever the breaker is operated manually or tripped on a fault.
    Difference from AL: AU indicates position, AL only signals a fault trip.

    3. SH - Shunt Release
    Function: This is an electromagnetic tripping module that requires an external control signal. When its coil receives a rated voltage signal (e.g., 220V AC/DC), it activates immediately to trip the breaker.
    Purpose: Used for remote electrical opening. Common in applications like fire alarm linkage, emergency stop systems, and Building Automation Systems (BAS) where remote power shutdown is required.
    Key Feature: It must be wired and requires a power signal to operate. Its trigger condition is the opposite of the Under-Voltage Release (UV).

    4. UV - Under-Voltage Release
    Function: This is an electromagnetic tripping module that requires a continuous power supply. It trips the breaker when the voltage across its coil drops below a set value (e.g., below 70% Un) or is lost completely.
    Purpose: Used to protect equipment from operating under low voltage conditions or to provide loss-of-power protection, preventing equipment from unexpectedly restarting when power returns.
    Key Feature: Requires continuous wiring. The coil is energized under normal operation; it trips upon loss of voltage.

    Technical Data

    SH5 - Shunt Release
    AU5 - Auxiliary Contact
    AL5 - Alarm Contact
    UV5 - Under Voltage Release
    OV5 - Over Voltage Release
    UV5+OV5 -

    Under Voltage+Over Voltage Release