Technical Data
| Standard | IEC61009-1 |
| Mode | Electronic/Electromagnetic |
| Type | A、AC |
| Tripping curve | BCD |
| Pole | 1P+N,3P+N |
| Rated voltage | 230/400V~ |
| Rated frequency | 50/60Hz |
| Rated current | 6-63A |
| Rated residual operating current(l△n) | 30、100、300mA |
| Residual operating current range | 0.5l△n~l△n |
| Ratedconditionalshort-circuit current(lnc) | 6KA/10KA |
| Energy limiting class | 3 |
| Electrical and Mechanical life | 20000 |
Overload Current Protection Characteristics
| Test Procedure | Type | Test Current | Initial State | Tripping or Non-tripping Time Limit |
Expected Result | Remark |
| A | B、C | 1.13In | cold | t≤1h | no tripping | |
| B | B、C | 1.45In | after test A | t<1h | tripping | The curent steadily rise to the specifed walue within5s |
| C | B、C | 2.55In | cold | 1s<t<60s(In≤32A) 1s<t<120s(In>32A) |
tripping | |
| D | B | 3In | cold | t≤0.1s | no tripping | Turn on theauxiliary switch toclose the current |
| C | 5In | |||||
| D | 10In | |||||
| E | B | 5In | cold | t<0.1s | tripping | Turn on theauxiliary switch toclose the current |
| C | 10In | |||||
| D | 20In |
Residual Current Operating Breaking Time
| type | In/A | I△n/A | Residual Current(I△)Is Corresponding To The Following Breaking Time(S) | |||
| ACtype | Any value | Anyvalue | In | 2In | 5In | 5A,10A,20A,50A |
| A type | >0.01 | 1.4In | 2.8In | 7In | ||
| 0.3 | 0.15 | 0.04 | 0.4 max breaking time | |||
| The general type RCBO whose current I△n is 0.03mA less can use 0.25A instead of 5I△n. | ||||||
Installation
| Protection degree | IP20 |
| Ambient temperature | -25~+40℃ |
| Storage temperature | -25~+70℃ |
| Terminal connection type | Cable/U-type busbar/Pin -type busbar |
| Terminal size top/bottom for cable | 25mm² |
| Tightening torque | 2.5N.m |
| Connection | Top and bottom |
Overall and mounting dimensioned chart

Product overview
Are you concerned about hidden leakage currents in aging wiring? Are you frustrated by frequent nuisance tripping caused by circuit overloads? Our RCBO is the definitive solution to these common and worrying electrical problems. It proactively detects even minor leakage currents resulting from insulation degradation—issues that are invisible to the naked eye—allowing for intervention before a hazardous situation develops. Its precise overload protection is calibrated to prevent fire risks from overheated cables while offering high immunity to the temporary inrush currents generated by appliances like motors and transformers, thus avoiding unnecessary power interruptions. By upgrading your electrical system with our RCBO, you are implementing a comprehensive and robust solution that effectively and permanently resolves core safety concerns, bringing your property's electrical safety into the 21st century.
Creating a New Chapter in Smart Electrical Partnerships
• Submit your needs for a tailored electrical solution
• A decade of technical expertise, 24/7 rapid response
• Every electrical challenge you face sparks our innovation

Modular DIN Rail Products
Smart Molded Case Circuit Breakers
PV Systems
Distribution Box