Leave Your Message

6KA/10KA residual current circuit breaker with overcurrent protection TDR7

Talemod TDR7 residual current circuit breaker with overcurrent protection simultaneously provides both overcurrent/short-circuit protection and earth leakage protection. The product is applied to the lines with AC 50/60Hz, rated voltage of 240V/415V, and rated working current up to 63A. The rated short-circuit breaking capacity has 6KA/10KA. The RCBO adopts modular design and complies with the standard IEC61009-1, has reliable performance, accurate protection characteristics, small size, and is suitable for industrial and commercial lighting distribution lines.

    Technical Data

    Standard IEC61009-1
    Mode Electronic
    Type A、AC
    Tripping curve BCD
    Pole 1P+N,2P3P3P+N,4P
    Rated voltage 230/400V~
    Rated frequency 50/60Hz
    Rated current 6-63A
    Rated residual operating current(l△n) 30、100、300mA
    Residual operating current range 0.5l△n~l△n
    Ratedconditionalshort-circuit current(lnc) 6KA/10KA
    Energy limiting class 3
    Electrical and Mechanical life 20000

    Overload Current Protection Characteristics

    Test Procedure Type Test Current Initial State Tripping or Non-tripping
    Time Limit
    Expected Result Remark
    A B、C 1.13In cold t≤1h no tripping
    B B、C 1.45In after test A t<1h tripping The curent steadily rise to the
    specifed walue within5s
    C B、C 2.55In cold 1s<t<60s(In≤32A)
    1s<t<120s(In>32A)
    tripping
    D B 3In cold t≤0.1s no tripping Turn on theauxiliary switch toclose the current
    C 5In
    D 10In
    E B 5In cold t<0.1s tripping Turn on theauxiliary switch toclose the current
    C 10In
    D 20In

    Residual Current Operating Breaking Time

    type In/A I△n/A Residual Current(I△)Is Corresponding To The Following Breaking Time(S)
    ACtype Any value Anyvalue In 2In 5In 5A,10A,20A,50A
    A type >0.01 1.4In 2.8In 7In
    0.3 0.15     0.04 0.4             max breaking time
    The general type RCBO whose current I△n is 0.03mA less can use 0.25A instead of 5I△n.

    Installation

    Protection degree IP20
    Ambient temperature -25~+40℃
    Storage temperature -25~+70℃
    Terminal connection type Cable/U-type busbar/Pin -type busbar
    Terminal size top/bottom for cable 25mm²
    Tightening torque 2.5N.m
    Connection Top and bottom

    Overall and mounting dimensioned chart

    TDR7-2.jpg

    product overview

    When a fault occurs, the reliability of your protective device is paramount. Our RCBO is constructed from robust engineering materials designed to withstand electrical stress, thermal cycling, and mechanical wear over its long service life. Its stable performance is guaranteed to remain consistent even in the face of power grid fluctuations and challenging environmental conditions, ensuring it is always ready to operate. To prove its mettle, every model undergoes exhaustive testing, including tens of thousands of mechanical durability cycles and rigorous short-circuit breaking tests that simulate extreme fault conditions. These tests validate its exceptional endurance and reliable tripping capability. This product is fundamentally built for long-term, stable operation, serving as a dependable guardian for your electrical system that you can count on day in and day out.

    Creating a New Chapter in Smart Electrical Partnerships

    • Submit your needs for a tailored electrical solution
    • A decade of technical expertise, 24/7 rapid response
    • Every electrical challenge you face sparks our innovation

    Send An Inquiry