Leave Your Message

4.5KA/6KA 18mm Width DPN Miniature Circuit Breaker TDM5N

Talemod TDM5N miniature circuit breaker is used for over-current protection and short circuit protection of all power line facilities and electrical equipment in buildings, and completing infrequent switching operation for the lines in normal circumstance. The product is applied to the lines with AC 50/60Hz, rated voltage of 240V, and rated working current up to 32A. The rated short-circuit breaking capacity has 4.5KA/6KA. The circuit breaker adopts modular design and complies with the standard IEC60898-1, has reliable performance, accurate protection characteristics, small size, and is suitable for industrial and commercial lighting distribution lines.

    Technical Data

    Item Data
    Standard IEC60898-1
    Rated current (In) 6-32A
    Pole 1P+N
    Rated voltage (Ue) 230V~
    Insulation voltage(U) 500V
    Rated frequency 50Hz
    Rated breaking capacity(Icn) 4.5KA
    Rated operating short circuit breaking capacity (Ies) 4.5KA
    Energy limiting class 3
    Tripping curve C,D
    Electrical and mechanical life 10000

    Overload Current Protection Characteristics

    Test
    procedure
    Type Test
    current
    Initial state Tripping or
    ntimeii
    Expected result Remark
    A C,D 1.13In Cold t≤1h Notripping
    B C,D 1.45In After test A t<1h Tripping The current steadily rise tothe specified value within5S
    C C,D 2.55In Cold 1s<t<60s(In≤32A) 1s<t<120s(In>32A) Tripping
    D C 5In Cold t≤0.1s Notripping Turn on the auxiliary
    switch to close the
    current
    D 10In
    E C 10In Cold t<0.1s Tripping
    D 201n

    未标题-1.jpg

    Installation

    Protection degree IP20
    Reference temperature for setting of thermal element 30℃
    Ambient temperature -25~+40℃
    Storage temperature -25~+70℃
    Terminal connection type Cable
    Terminal size top/bottom for cable 10mm²
    Tightening torque 2.5N.m
    Connection   Top and bottom

    Combination with accessories

    Auxillary contact YES
    Alarm contact YES
    Shunt release YES
    Under voltage release YES

    Overall and mounting dimensioned chart