Leave Your Message

10KA residual current circuit breaker with overcurrent protection TDR5

Talemod TDR5 residual current circuit breaker with overcurrent protection simultaneously provides both overcurrent/short-circuit protection and earth leakage protection. The product is applied to the lines with AC 50/60Hz, rated voltage of 240V, and rated working current up to 50A. The rated short-circuit breaking capacity has 10KA. The RCBO adopts modular design and complies with the standard IEC61009-1, has reliable performance, accurate protection characteristics, small size, and is suitable for industrial and commercial lighting distribution lines.

    Technical Data

    Standard IEC61009-1
    Mode Electronic
    Type A、AC
    Tripping curve BCD
    Pole 1P+N
    Rated voltage 240V~
    Rated frequency 50/60Hz
    Rated current 6-50A
    Rated residual operating current(l△n) 30、100、300mA
    Residual operating current range 0.5l△n~l△n
    Ratedconditionalshort-circuit current(lnc) 10KA
    Energy limiting class 3
    Electrical and Mechanical life 20000

    Overload Current Protection Characteristics

    Test Procedure Type Test Current Initial State Tripping or Non-tripping
    Time Limit
    Expected Result Remark
    A B、C 1.13In cold t≤1h no tripping
    B B、C 1.45In after test A t<1h tripping The curent steadily rise to the
    specifed walue within5s
    C B、C 2.55In cold 1s<t<60s(In≤32A)
    1s<t<120s(In>32A)
    tripping
    D B 3In cold t≤0.1s no tripping Turn on theauxiliary switch toclose the current
    C 5In
    D 10In
    E B 5In cold t<0.1s tripping Turn on theauxiliary switch toclose the current
    C 10In
    D 20In

    Residual Current Operating Breaking Time

    type In/A I△n/A Residual Current(I△)Is Corresponding To The Following Breaking Time(S)
    ACtype Any value Anyvalue In 2In 5In 5A,10A,20A,50A
    A type >0.01 1.4In 2.8In 7In
    0.3 0.15     0.04 0.4             max breaking time
    The general type RCBO whose current I△n is 0.03mA less can use 0.25A instead of 5I△n.

    Installation

    Protection degree IP20
    Ambient temperature -25~+40℃
    Storage temperature -25~+70℃
    Terminal connection type Cable/U-type busbar/Pin -type busbar
    Terminal size top/bottom for cable 10mm²(top)/25mm²(bottom)
    Tightening torque 1.2N.m(top)/2.5N.m(bottom)
    Connection Top and bottom

    Overall and mounting dimensioned chart

    TDR5-2.jpg

    Product overview

    Our RCBO is meticulously designed and manufactured in strict compliance with major international safety standards, such as IEC 61009, serving as a symbol of quality and regulatory conformity. Each unit undergoes rigorous factory testing to verify its sensitive residual current operation and reliable overcurrent breaking capacity. These tests ensure that the device will perform as intended in real-world fault conditions. By incorporating this RCBO into your electrical installations, you significantly simplify the process of adhering to national electrical codes and regulations, thereby reducing compliance risks and potential liabilities. Choosing this product means selecting a safety device that is backed by authoritative certifications and one that can be fully trusted to provide consistent, reliable protection for people and circuits, as verified by independent testing and quality control protocols.

    Creating a New Chapter in Smart Electrical Partnerships

    • Submit your needs for a tailored electrical solution
    • A decade of technical expertise, 24/7 rapid response
    • Every electrical challenge you face sparks our innovation

    Send An Inquiry